t <br />Cabarrus County <br />Board of Elections Project <br />REQUEST FOR INFORMATION Date Created: 01120/11 <br />CM Black Construction Company, Inc. Date Required: by Addendum #1 <br />Architect: Yates- Chreitzberg- Hughes Arch. <br />Submitted By: Emmitt H. Black <br />Attn: Mike Chreitzberg / Ed Estridge <br />Architect Address: 145 Union Street South <br />Concord, NC 28025 <br />Pre -Bid RFl# 004 <br />INFORMATION REQUESTED: <br />Scope Reference: Electrical (1 sheet attached) <br />Drawing and detail reference: E -4 (DT -300 for OCs) <br />Specification section and paragraph: <br />INFORMATION REQUESTED <br />I have attached a cut sheet for the DT -300 which Is specified for OCs on the drawing E -4. The <br />DT -300 has a limit of 2 on 1 power pack, and the height limit Is 10'. 90% of the rooms are 11'4 <br />and or exposed to trusses, I have searched for a OC that would work, but other ones just go to <br />9' and 8'.1 feel this is something the A/E needs to be informed of. <br />Signed: Emmitt Black / LS <br />RESPONSE <br />The DT -300 can be used but the coverage will be reduced somewhat due to the ceiling <br />height, therefore, more occupancy sensors are shown on the plan. Per the manufacturer, <br />the BZ series power packs can power up to 3 occupancy sensors. <br />Answered By: ,_Byron Ford Date: _1/25111 <br />U �u � Tr dX cal & ' 61YO (' Int - <br />Answered By: _Ed Estridge <br />[ 7 kid)(two I��cCo <br />=Vr MAILED <br />G -3 <br />Date: _1/25/11 <br />Attachment number 3 <br />Page 262 <br />