SECTION 07541 — TPO ROOFING SYSTEM MODIFICATIONS
<br />8. On page 07541 -1, under PART 1 — GENERAL, SUBMITTALS, delete the third paragraph In its entirety as
<br />submittal of wind uplift calculations will not be required.
<br />9. On page 07541 -6, under PART 3 — EXECUTION, WALKWAYS add the following sentence: "Do not install
<br />walkway material over seams in roof membrane or over seams between flashing and roof membrane."
<br />SECTION 08410 — ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS
<br />10. On page 08410 -3, under PART 2 — PRODUCTS, in the third paragraph change the EFCO storefront model
<br />number to "403."
<br />SECTION 09510 — ACOUSTICAL PANEL CEILING SYSTEMS
<br />11. On page 09510 -5, under PART 3 — EXECUTION, INSTALLATION, add the following to the end of the 4 t '
<br />paragraph: "Coordinate the placement of hanger wire with locations of above ceiling equipment, service access
<br />locations, access doors, etc. so as not to restrict access to these Items"
<br />FIRE PROTECTION
<br />SECTION 15300 — FIRE PROTECTION GENERAL
<br />12. On page 15300 -4, under 1.8 PROTECTION OF SERVIES AND EQUIPMENT, B, add the following: "Protection of
<br />materials or equipment shall be maintained throughout construction by FP contractor. Temporary caps or
<br />covering /wrapping of material Is acceptable.
<br />13. On page 15300 -10, under 1.20 PAINTING, add the following sentence: `Painting shall be by the painting
<br />subcontractor under Division 9."
<br />14. On page 15300 -12, under 2.3 SPRINKLER AND STANDPIPE PIPING, ABOVE GROUND, A.13.1.a,1, change the
<br />second sentence to read: "Victaulic Style 009 -EZ or Victaulic 009H,"
<br />15. On page 15300 -12, under 2.4 VALVES FOR FIRE PROTECTION SYSTEMS, A, B, C and D, add "Viking and
<br />Reliable" as acceptable equal manufacturers.
<br />SECTION 15315 — WET -PIPE SPRINKLER SYSTEM
<br />16. On page 15315 -1, under 1.4 Submittal, D, revise the sentence to read: "Design Data: Submit design calculations
<br />signed and sealed by a professional engineer or a NICET Level III Designer."
<br />17. On page 15315 -2, under 1.7 QUALIFICATIONS, C, revise the system to read: "Design system under direct
<br />supervision of Professional Engineer of NICET Level 111 Designer experienced in design of this Work and licensed
<br />at Project location (state)."
<br />18. On page 15315 -3, under 2.1 SPRINKLERS, A, B & C, include Viking, Tyco, Globe and Reliable are accepted
<br />equals.
<br />19. On page 15315 -3, under 2.1 SPRINKLERS, A.1, change type to read: `Concealed type with matching
<br />escutcheon plate."
<br />20. On page 15315 -3, under 2.2 PIPING SPECIALTIES, A, add "Viking and Reliable" as accepted equals.